OWN ENERGY ME

SUN-8/10/12/15K-SG01HP2-US-AM2

Three Phase Hybrid Inverter | 8-15kW | 2 MPPT | HV Battery Supported

SUN-14/15/16/18/20K-SG05LP3-EU-SM2 (3 String Version)
Remotely shutdown function
Smart Monitoring Platform

Thanks to the smart monitoring platform, Deye full series inverter products support remotely shutdown immediately when accident occurs.Setting parameters and FW update remotely, which makes PV plant O&M easier.

solar-inverter1 description
  • 100% unbalanced output
  • AC couple to retrofit existing solar system
  • Max. 10 pcs parallel for on-grid and off-grid operation; Support multiple batteries parallel
  • Max. charging/discharging current of 50A
  • High voltage battery, higher efficiency
  • 6 time periods for battery charging/discharging
  • Support storing energy from diesel generator
Technical Specifications
Model SUN-8K-SG01HP2
-US-AM2
SUN-10K-SG01HP2
-US-AM2
SUN-12K-SG01HP2
-US-AM2
SUN-15K-SG01HP2
-US-AM2
Battery Input Data
Battery Type  Lithium-ion
Battery Voltage Range (V) 160-500
Max. Charging Current (A) 50
Max. Discharging Current (A) 50
Charging Strategy forLi-ion Battery Self-adaption to BMS
Number of Battery Input 1
PV String Input Data
Max. PV Access Power (W)
16000 20000 24000 30000
Max. PV Input Power (W) 12000 15000 18000 22500
Max. PV Input Voltage (V) 550
Start-upVoltage (V) 180
MPPT Voltage Range (V)  150-500
Rated PV Input Voltage (V) 380
Max. Operating PV Input Current (A) 26+26
Max. Input Short-Circuit Current (A) 39+39
No. of MPP Trackers/No. of Strings MPP Tracker 2/2+2
AC Input/Output Data
Rated AC Input/Output Active Power (W) 8000 10000 12000 15000
Max. AC Input/Output Apparent Power (VA) 8000 10000 12000 15000
Rated AC Input/Output Current (A) 33.4 41.7 50 62.5
Max. AC Input/Output Current (A) 33.4 41.7 50 62.5
Max. Continuous AC Passthrough (grid to load) (A) 150
Peak Power (off-grid) (W) 1.5 times of rated power, 10s
Power Factor Adjustment Range 0.8 leading to 0.8 lagging
Rated Input/Output Voltage/Range (V) 120/240, 208   0.85Un-1.1Un
Rated Input/Output Grid Frequency/Range(Hz) 60/55-65
Grid Connection Form 2L+N+PE
Total Current Harmonic Distortion THDi <3% (of nominal power)
DC Injection Current <0.5% In
Efficiency
Max. Efficiency 97.6%
Euro Efficiency 97.0%
MPPTEfficiency >99%
Equipment Protection
Integrated
DC Reverse Polarity Protection, AC Output Overcurrent Protection, Thermal Protection, AC Output Overvoltage Protection, AC Output Short Circuit Protection, DC Component Monitoring, Arc Fault Circuit Interrupter (optional), Anti-islanding Protection, DC Switch, Insulation Impedance Detection, Residual Current Detection
Surge Protection Level TYPE II(DC),TYPE II(AC)
Interface
Communication Interface RS485/RS232/CAN
Monitor Mode GPRS/WIFI/Bluetooth/4G/LAN(optional)
General Data
Operating Temperature Range () -40 to +60, >45℃ Derating
Permissible Ambient Humidity 0-100%
Permissible Altitude 2000m
Noise (dB) ≤55
Ingress Protection(IP) Rating TYPE3R
Inverter Topology Non-Isolated
Over Voltage Category OVC II(DC), OVC III(AC)
Cabinet Size (WxHxD mm) 436×680×277.5 (Excluding Connectors and Brackets)
Weight (kg) 34.8
Type of Cooling Intelligent Air Cooling
Warranty 5 Years/10 Years
the Warranty Period Depends the Final Installation Site of Inverter, More Info Please Refer to Warranty Policy
Grid Regulation IEEE 1547.1,SRD V2.0
Safety / EMC Standard FCC, UL 1741